General Features
Type DIN-Rail Mount
Case Metal-Aluminum
Operating temperature -25 … +75
Power Protection and IO Isolation Yes
Protocol Support IEC 60870-5-101/103/104 and MODBUS
Programming
IEC 61131-3 Compatible Programming Yes
Programming Editor Mikrodev Telediagram Application
Supportted Protocols with Telediagram Editor IEC61850, IEC 60870, DNP3 ve MODBUS
Drag and drop programming with Function block diagram (FBD)           Yes
Real-time monitoring/controlling of process data Yes
Offline simulation Yes
Programming with standard USB cable Yes
Programming over TCP Yes
Remote firmware upgrade Yes
View process data over web-server Yes
PID and ON-OFF Control Blocks Library Yes
Math Floating Points Blocks Library Yes
Communication Protocols
MODBUS TCP Master/Slave
MODBUS RTU Master/Slave
IEC 60870-5-104 Slave
IEC 60870-5-101 Slave
Gateway Mode Yes
IoT Protocols MQTT Client
IP Protocols TCP, UDP, NTP, SNTP, HTTP, TFTP, DHCP, DNS
Maximum Socket Connection Count
Max Number of Server Sockets 16
Number of Client Sockets per TCP Server Socket 16
Max Number of Client Sockets 32
Communication Ports
Ethernet 2 port, 10/100 Mbps
RS485 2 port, Galvanic Isolation
RS232 2 port, Optical Isolation
USB 2 port
Integrated GSM/GPRS Modem Class 12, Quad-Band 850 / 900 / 1800 / 1900 MHz
Integrated UMTS/HSPA+ modem Max.14.4Mbps (DL)/Max.5.76Mbps (UL)
Integrated GPS GLONASS/GNSS alıcı
Integrated I/O Ports
Digital Input 24, Optical isolation, 0-50V DC, 10 kHz
Digital Output 8, Optical isolation, Max 50V DC, [email protected] DC
Relay Output 4, [email protected] VAC
Analog Input 8, 16 bit, 0-10V or 0-20mA, Optical isolation
Analog Output 4, 14 bit, 0-10V or 0-20mA, Optical isolation
IO Expansion Capability
Digital Input Up to 1024 points
Digital Output Up to 1024 points
Analog Input Up to 128 points
Analog Output Up to 128 points
RTD/Temperature Input Up to 128 points
Event Recording
Time Tag With Event Records Yes
Resolution of Event Time Tag 1 ms
Event Recording Capacity 20000
Data Logger Functionality
SD Card Support Micro SD Card
Programmable data logging trigger functions Yes
Retentivity
Protecting the last values of process data in case of power cut Yes
Retentive Memory Capacity 1000 Blocks/RegisterType
Real Time Clock and Calendar
Real-time clock Integrated
RTC battery CR2032 Lithium, battery life: 4 years
Battery status/level reading functions Yes
NTP Client Yes
DNP3 Time Synchronization Yes
IEC101/IEC104 Time Synchronization Yes
GPS Time Synchronization Yes
Update over MODBUS Yes
LED Signals
POWER 1 LED Green
WARNING/ERROR 1 LED Green
RUNNING STATUS 1 LED Green
RS232-1 2 LED, Tx-Rx, Green
RS232-2 2 LED, Tx-Rx, Green
RS485-1 2 LED, Tx-Rx, Green
RS485-2 2 LED, Tx-Rx, Green
Digital Inputs 24 LED Blue
Digital Output 8 LED Blue
Relay Output 4 LED Blue
Standards
IEC 60255-5 2.5 kV isolation
IEC 61000-4-2 6 kV direct, 8 kV air discharge
IEC 61000-4-6 RF field affect 10 Vrms (150kHz - 80MHz)
IEC 61000-4-18 2.5 kV (400/s period with 1 Mhz electromagnetic wave)
Environmental Conditions
Operating Temperature -25 / +75 C
Storing Temperature -30 / +80 C
Electrical Wiring
On inputs and outputs Demountable terminal block with screw, (pitch 5.08 mm)
On 24V DC input Demountable terminal block with screw, (pitch 5.08 mm)
Supply
Supply Voltage 12...36 VDC
Supply Current 100 mA @ 24 VDC
Warranty
Duration 24 Months
CE Sign Yes

ELECTRICAL ENERGY AUTOMATION

MIKRODEV RTU300 and RTU400 series devices are able to read and control the Smart Electric Devices (Protection relays, recloser cutters, energy and quality analyzers, etc.) in industry with IEC 61850, MODBUS TCP and MODBUS RTU protocols which are the industrial standards for communication. It can also communicate with SCADA or control center software via IEC 60870, DNP3 and MODBUS TCP protocols. With its easy, flexible and fast programming capabilities and I/O capability expandable up to 1024 points, MIKRODEV RTU products are preferred in electrical energy applications.

CLEAN AND WASTE WATER MARKET

MIKRODEV RTU products are used in the remote monitoring and control of pumping stations, tanks, wells, pipelines, meters and flow meters, valves, dosing and water quality measuring stations.

According to the Master/Slave operating principle, they can create simultaneous and multiple communication channels between stations such as wells, tanks, promotion centers in water systems. In this way, the entire water network is managed in a distributed manner.

Even if the central SCADA is out of service, the stations in the field continue to work by communicating with each other. Once SCADA is active again, past events and data can be forwarded to the system without loss of data with time-tagged messages of IEC104 and DNP3.

Mikrodev MP200G Teknik Çizimi
Product Code GSM ETH RS485 RS232 DI DO AI AO MODBUS IEC101/104 DNP3 IEC 61850
RTU430 3G 2 2 2 24 8 8 4 Yes Yes . .  

Software

Telediagram Software  